4725.3350 INTERCONNECTIONS AND CROSS CONNECTIONS.

No connection between a well or boring and another well, boring, water supply system, or contamination source is allowed unless the connection is:

A.

protected by an air gap as described in UPC section 603.3.1 as incorporated by part 4714.0050;

B.

protected with a backflow prevention device as specified in UPC sections 603.0 to 603.5.23.4 as incorporated by part 4714.0050;

C.

protected with a backflow prevention device as specified in parts 1505.2100 to 1505.2800 if the well is an irrigation well used for chemigation; or

D.

between wells or borings that meet the construction standards of this chapter, are used for the same purpose, and have equivalent water quality.

This part does not apply to a water distribution system after the pressure tank; however, this part does not exempt water distribution systems otherwise regulated by chapter 4714.